CPS-EC1500
Model | CPS-EC1500(R2) | ||||||||
Power | 1500W | ||||||||
Nominal AC Input | 230Vac | ||||||||
Input Range AC | 186-264Vac | ||||||||
Input Range DC | 250-375Vdc | ||||||||
Hold-Up Time | 20ms | ||||||||
Inrush Current | Electronic Inrush Current Limiter 9,8Arms | ||||||||
Output Voltage | 24V | 36V | 48V | 60V | 72V | 110V | 150V | 220V | 400V |
Output Current | 62,5A | 41,7A | 31,2A | 25A | 20,8A | 13,6A | 10A | 6,8A | 4,6A |
DC Voltage Setting | 24-30V | 36-45V | 48-58V | 60-75V | 72-90V | 110-137V | 132-180V | 220-264V | 330-400V |
DC Current Setting | 31,3-62,5A | 20,9-41,7A | 15,6-31,2A | 12,5-25,0A | 10,4-20,8A | 6,8-13,6A | 5,0-10,0A | 3,4-6,8A | 2,3-4,6A |
Ripple & Noise PP | 40mV | 40mV | 120mV | 150mV | 200mV | 300mV | 400mV | 400mV | 400mV |
Efficiency | 94% | ||||||||
Base load | Idling-proof | ||||||||
Short Circuit | Continuous | ||||||||
Cooling | Controlled stepless fan from EBM Papst (Germany) | ||||||||
Dimensions (WxHxD) | 250x156x115mm | ||||||||
Safety Standards | EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1 | ||||||||
Input to Output Isolation | 3000Vac | ||||||||
EMI/EMS | EN55032 conducted class B / radiated class A, EN61000-6-3 | ||||||||
EMS | EN61000-6-2 | ||||||||
MTBF | 400.000h | ||||||||
Power Good Relay | Yes | ||||||||
Boost Charge Mode | Yes | ||||||||
Remote Shutdown | Yes | ||||||||
Inhibit (Interlock) | Yes | ||||||||
Current Monitoring | Yes | ||||||||
Sense Comensation | Yes |