CPS-EP3000 3000W 19-Inch Rack-Mount & Wall-Mount

 

 

Specifications

  • V programming with internal poti
  • OCP & OVP
  • Current Share Bus for N+1 parallel operation
  • Sense Mode
  • Current Monitoring
  • Remote Shutdown
  • Inhibit (Interlock)
  • DC & AC Power Good Relay open/center/close
  • Fan Monitoring
  • Temperature OT alarm
  • 6kW in a 2U & 10kW in a 3U subframe
  • Hard mount in 90° steps
  • Optional LAN Interface DIGI3201

 

STEP STEP Dateien (ZIP)

 

 

 

CPS-EP3000

Series CPS-EP3000(R2)
Continuous Power 3000W
Nominal Input Voltage 230Vac
Input Voltage Range AC 184-264Vac
Input Voltage Range DC 250-375Vdc
Hold-up Time 20ms
Inrush Current AC Electronic Inrush Limiter 14,6Arms
Startautomatic Softstart 100ms
Model CPS-EP3000.012 CPS-EP3000.024 CPS-EP3000.036 CPS-EP3000.048 CPS-EP3000.072 CPS-EP3000.110 CPS-EP3000.220
GTIN / EAN 4262552171935 4262552171942 4262552171959 4262552171966 4262552171973 4262552171980 4262552171997
Vout 12V 24V 36V 48V 72V 110V 220V
Vout progr. with poti 2-15V 24-30V 30-45V 45-58V 58-90V 90-150V 200-300V
Aout 200,0A 125,0A 83,0A 62,5A 41,6A 27,2A 13,6A
Ripply & Boise mVpp 35mV 35mV 35mV 75mV 100mV 200mV 400mV
Effeciency 94%
Basic Load Idling-proof
Short Cicuit Protection Continuous
Cooling Stepless controlled fans from EBM-Papst flow front-to-rear, Fan Fail message
Dimensions 84x126,4x444mm, 2U or 3U Embedded or hard mount in 90° steps
Safety Standards EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Input- /Output Isolation 3000Vac
EMI EN55032 class B and class A depending on models
EMS EN61000-6-2,3,4
MTBF 500.000h
Current Monitoring Yes
Inhibit (Interlock) Yes
DC Power Good Relay Yes
AC Power Good Relay Yes
Sense Compensation Yes
Remote Shutdown Yes
Continuous Mode Yes
Current Share Bus Yes
Fan Failure Monitor Yes
Temperature Monitor Yes