ESB00323 (3PH)

  • Inrush Current Limiter (ESB) DIN-Rail TS35mm
  • Designed for rough industrial environment
  • Built-in switch mode power supply
  • Phase Monitor (under voltage / loss / asymmetry)
  • Ton limiting time & Toff low voltage delay time adjustable
  • Advanced passive cooling with over dimensioned limiting resistors
  • Limiting of each phase completely independent 

Product Information (PDF)

STEP-Datei (STP)

 

 

 

ESB00323A.T (3PH)

ModelESB00323A(R2)
Limiting Peak current68,6A Ton adjustable 70 to 240ms
Limiting RMS-value48A Ton adjustable 70 to 240ms
Limiting Cycle Interval60s
Low Voltage DetectionToff adjustable 60 to 170ms
Input Voltage3x 170 - 575Vac or 2x 170 - 575Vac, 47 - 63Hz
Nominal voltage3x 200/400/500Vac selectable
AC Continuous Current3x 32A
Load capacity3x 2000uF
ConnectorsSpring-type-terminal 0,5 -16mm², 22 - 8AWG
Ambient Opearting Temperature-20°C - +45°C no derating
CoolingNatural convection
Dimensions (WxHxD)95 x 155 x 122mm
Safety StandardsEN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Special FeaturesIntegrated & complete phase monitor
 Asymmetry, phase lost, phase sequence
 Accuracy ±6%, independent from ambient temperature
 Extending monitoring
 Each phase limited independently
 Ballast and capacitive loads
 Active & precise measuring circuit
 Bypass circuit each phase
 Built in switch mode power supply



 

ESB00323B.T (3PH)

ModelESB00323B(R2)
Limiting Peak current68,6A Ton adjustable 70 to 240ms
Limiting RMS-value48A Ton adjustable 70 to 240ms
Limiting Cycle Interval60s
Low Voltage DetectionToff adjustable 60 to 170ms
Input Voltage3x 170 - 460Vac or 2x 170 - 460Vac, 47 - 63Hz
Nominal voltage3x 200/400Vac selectable
AC Continuous Current3x 32A
Load capacity3x 2000uF
ConnectorsSpring-type-terminal 0,5 - 16mm², 22 - 8AWG
Ambient Opearting Temperature-20°C - +60°C no derating
CoolingNatural convection
Dimensions (WxHxD)95 x 155 x 122mm
Safety StandardsEN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Special FeaturesIntegrated & complete phase monitor
 Asymmetry, phase lost, phase sequence
 Accuracy ±6%, independent from ambient temperature
 Extending monitoring
 Each phase limited independently
 Ballast and capacitive loads
 Active & precise measuring circuit
 Bypass circuit each phase
 Built in switch mode power supply