PSM02202

  • Rack Mount 1phase Fixed Output
  • Active inrush current protection
  • 8KV strange

Product Information (PDF)

Datenblatt PSM02202 EN60950 (PDF)

 

 
 

PSM02202

Model PSM02202
Power 220W
Nominal Input Voltage 230Vac
Input Range AC 184... 264Vac
Input Range DC 250... 300Vdc
Input Frequency 47... 63Hz
Hold-Up Time 50ms
Inrush Current Protection < 24Apeak / 17Arms active protection ±6%
Autostart Soft start 20ms
Output Voltage U1 + 12V + 15V  
Output Voltage U2 - 12V - 15V  
Output Voltage U3 + 24V + 30V U1 and U2 connectable
Ripple & Noise mVss U1 15mV 15mV  
Ripple & Noise mVss U2 15mV 15mV  
Ripple & Noise mVss U3 30mV U1 and U2 connectable
Output Current I1 12A 10A  
Output Current I2 12A 10A  
Output Current I3 9,2A 7,3A U1 and U2 connectable
Power Boost <=60°C/60s 264W
Stability at Load Switch ±1%
Transient Time < 1ms
Efficiency 91%
Basic Load Idling-proof
Short Circuit Protected Continuous
Ambient Operating Temperature -20°C... +70°C
Cooling Natural Convection
Temperature Monitoring Yes
Dimensions (WxHxD) 3U 8HP 160mm
IP-Range IP20
Safety IEC EN60950-1 EN50178 EN60204-1
Safety class 1(A) VDE0100 VDE0805
Input to Output Insulation 3000Vac
Climatic Class, Humidity 3k3, 90% non condensing
EMI EN55022B EN61000-3-2A
EMS EN61000-6-2,3
MTBF IEC61709 450000h
Remote Shutdown Yes
Features 8KV/2.5kHz input transient protection
Ordering options Protective coating
Options See datasheet