ESB201.LED

  • Inrush Current Limiter (ESB) for LED Power Supply and Electronic Ballast

STEP Datei (STP)

 

 
 

ESB201.LED.230Vac

Model ESB201.LED.230Vac(R2)
Limiting Peak current 48A for Ton=300ms
Limiting RMS-value 33,9A for Ton=300ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=550ms
Input Voltage 184 - 264Vac, 16 1/3 - 440Hz 1PH
Nominal voltage 220 - 240Vac
AC Continuous Current 16A input/output
Load capacity 6000uF
Connectors Spring-type-terminal 0,5 - 6mm²
Ambient Opearting Temperature -20 - +C45°C no derating
Cooling Natural convection
Dimensions (HxDxW) 35,4 x 23,5 x 260mm
Safety Standards EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Special Features Temperature protected (fuse)
  Safety covered terminals against electrical shock
  Fire protected
  Accuracy ±6%, independent from ambient temperature
  Ballast and capacitive loads
  Bypass circuit
  4000m / 13123 ft. above sea level



 

ESB201.LED.115Vac

Model ESB201.LED.115Vac(R2)
Limiting Peak current 43A for Ton=500ms
Limiting RMS-value 30,4A for Ton=500ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=550ms
Input Voltage 90 - 130Vac, 16 1/3 - 440Hz 1PH
Nominal voltage 110 - 120Vac
AC Continuous Current 16A
Load capacity 10000uF
Connectors Spring-type-terminal 0,5 - 6mm²
Ambient Opearting Temperature -20°C - +45°C no derating
Cooling Natural convection
Dimensions (WxHxD) 35,4 x 23,5 x 260mm
Safety Standards EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1
Special Features Temperature protected (fuse)
  Safety covered terminals against electrical shock
  Fire protected
  Accuracy ±6%, independent from ambient temperature
  Ballast and capacitive loads
  Bypass circuit
  4000m / 13123 ft. above sea level