DISTRIBUTION

 

x

ESB101

  • Inrush Current Limiter (ESB) DIN-Rail TS35mm
Product Information (PDF) STEP-Datei (STP) Data Sheet (PDF)

 




ESB101.LED.230Vac

Model ESB101.LED.230Vac
Limiting Peak current 48A for Ton=300ms
Limiting RMS-value 33,9A for Ton=300ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=550ms
Input Voltage 184... 265Vac 16 1/3... 440Hz 1PH
Nominal voltage 220... 240Vac
AC Continuous Current 16A input/output
Load capacity 6000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C … +70°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.LED.115Vac

Model ESB101.LED.115Vac
Limiting Peak current 43A for Ton=500ms
Limiting RMS-value 30,4A for Ton=500ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=550ms
Input Voltage 90... 130Vac 16 1/3... 440Hz 1PH
Nominal voltage 110... 120Vac
AC Continuous Current 16A
Load capacity 10000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C... +0°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.16

Model ESB101.16
Limiting Peak current 16A for Ton=300ms
Limiting RMS-value 11,3A for Ton=300ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=500ms
Input Voltage 184... 265Vac 16 1/3... 440Hz 1PH
Nominal voltage 220... 240Vac
AC Continuous Current 16A input/output
Load capacity 1500uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C … +70°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.23

Model ESB101.23
Limiting Peak current 23A for Ton=300ms
Limiting RMS-value 16,3A for Ton=300ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=500ms
Input Voltage 184... 265Vac 16 1/3... 440Hz 1PH
Nominal voltage 220... 240Vac
AC Continuous Current 16A input/output
Load capacity 2000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C... +70°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.23S

Model ESB101.23S
Limiting Peak current 23A for Ton=500ms
Limiting RMS-value 16,3A for Ton=500ms
Limiting Cycle Interval 1400ms (3x/minute)
Low Voltage Detection Toff=800ms
Input Voltage 184... 265Vac 16 1/3... 440Hz 1PH
Nominal voltage 220... 240Vac
AC Continuous Current 16A
Load capacity 2000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C... +0°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.23S.115Vac

Model ESB101.23S.115Vac
Limiting Peak current 23A for Ton=500ms
Limiting RMS-value 16,3A for Ton=500ms
Limiting Cycle Interval 1400ms (3x/minute)
Low Voltage Detection Toff=900ms
Input Voltage 90... 130Vac 16 1/3... 440Hz 1PH
Nominal voltage 110... 120Vac
AC Continuous Current 16A
Load capacity 4000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C... +0°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level



ESB101.33

Model ESB101.33
Limiting Peak current 33A for Ton=300ms
Limiting RMS-value 23,3A for Ton=300ms
Limiting Cycle Interval 900ms (3x/minute)
Low Voltage Detection Toff=800ms
Input Voltage 184... 265Vac 16 1/3... 440Hz 1PH
Nominal voltage 220... 240Vac
AC Continuous Current 16A
Load capacity 4000uF
Connectors Spring-type-terminal 0,5... 6mm²
Ambient Opearting Temperature -40°C... +70°C no derating
Cooling Natural convection
Dimensions (WxHxD) 36,5 x 62 x 110mm
Special Features Temperature protected (fuse)
  Fire protected
  Accuracy ±5%, independent from ambient temperature
  Capacitive loads
  Bypass circuit
  4000m / 13123 ft. Above sea level